FLAME SENSOR DIRTY
Lennox · EL296V Elite Series 96% AFUE Two-Stage Variable Speed Gas Furnace
The flame sensor rod is coated with carbon, oxidation, or silica deposits, preventing flame current detection. Causes gas valve shutoff within a few seconds of ignition. Symptoms: burner lights, runs for 3–8 seconds, then shuts off. Fix: remove flame sensor (one screw) and clean with fine emery cloth until rod is shiny. Flame current should read ≥1.0 µA DC. This is the #1 DIY Lennox furnace repair.
Error FLAME SENSOR DIRTY on the Lennox EL296V Elite Series 96% AFUE Two-Stage Variable Speed Gas Furnace means: Flame Sensor Fouled / Failed. The top-ranked community fix is “Test and Replace the Flame Sensor if Faulty” (medium difficulty, ~45 min, DIY cost: $40-$60). 2 community-ranked fixes available below.
Published February 2026 · 2 fixes · furnace
Content is based on manufacturer service documentation, community repair experience, and OEM technical bulletins. Always verify with your owner's manual.Learn about our editorial standards.
While many furnace repairs can be done safely at home, consider hiring a qualified technician if:
Average professional repair cost for this issue: $120-$180.
No Previous Fault Code Stored
Blower Motor Calibration Fault
Auxiliary Limit Switch Open
Inducer Motor Fault
Communicating System Fault
System Lockout — Retries Exhausted
Pressure Switch Stuck Closed
Pressure Switch Open — Did Not Close
The Lennox EL296V Elite Series 96% AFUE Two-Stage Variable Speed Gas Furnace has 8 other known error codes:
Error code FLAME SENSOR DIRTY also appears on 3 other Lennox models: