ALERT 2
Lennox · XP21 Dave Lennox Signature Collection 20 SEER Heat Pump
Communication lost between the thermostat and the indoor unit (furnace or air handler). Check communicating wiring from thermostat to furnace/air handler IFC board. Check IFC board fuse. Verify indoor unit has power. Common cause: loose connection at the IFC board communicating terminals.
Error ALERT 2 on the Lennox XP21 Dave Lennox Signature Collection 20 SEER Heat Pump means: Communication Loss — Indoor Unit. The top-ranked community fix is “Test and Replace IFC Board Fuse or IFC Board if Faulty” (medium difficulty, ~60 min, DIY cost: $5-$20). 2 community-ranked fixes available below.
Published February 2026 · 2 fixes · heat pump
Content is based on manufacturer service documentation, community repair experience, and OEM technical bulletins. Always verify with your owner's manual.Learn about our editorial standards.
While many heat pump repairs can be done safely at home, consider hiring a qualified technician if:
Average professional repair cost for this issue: $200-$350.
High Pressure Switch Open
Low Pressure Switch Open
Compressor Thermal Overload
Short-Cycle Protection
Communication Loss — Outdoor Unit
High Pressure Protection — Outdoor Unit
Low Pressure Protection — Outdoor Unit
Compressor Discharge Temperature High
The Lennox XP21 Dave Lennox Signature Collection 20 SEER Heat Pump has 8 other known error codes:
Error code ALERT 2 also appears on 3 other Lennox models:
Ad Space — banner
Replace ADSENSE_PUBLISHER_ID in AdUnit.tsx